Start-Up Operation
Multiple Systems With Multiple
Evaporators (Requires A Smart
Controller)
Check all wiring connections to be sure
they are correct and tight.
On the condensing units
- Check setting of time delay relay.
It should be set at 1 minute
(the second marker).
- Check the low pressure switch
setting on freezer units. It must be set
to 0 psig cut-out, 10 psig cut-in to
allow positive start and operation,
especially in cold ambient. This
can be changed to a higher value in
warmer climates. On cooler units,
the low pressure switch has a xed
setting and cannot be adjusted.
Turn power on.
S S
S
M
CU
S S
S
M
CU
S S
S
M
CU
M S
S
S
CU
SMART
CONTROLLER
SYSTEM 1
SYSTEM 2 SYSTEM 3
SYSTEM 4
M = Master Evaporator S = Slave Evaporator CU = Condensing Unit
MULTIPLE SYSTEM CONNECTION
(See Smart Controller instruction manual for more details)
On the MASTER evaporator
- DO NOT REMOVE the room sensor
from any evaporator
On the SLAVE evaporators. All Beacon II
boards are shipped with the factory
default as a “MASTER” evaporator.
- Each SLAVE evaporator must be
changed to identify it as a SLAVE.
Use the “PROGRAM REVIEW
button to scroll until “SLA appears,
then use the “SELECT” knob to
select “YES” then press “ENTER.”
Use the Beacon II Smart Controller to
set system parameters. See Beacon
II Smart Controller installation
instructions for more details.